Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR04055
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/18/2009 | INSP - FULL | Approved | SPRINKLER HEAD HAS BEEN DROPPED IN SERVICE OFFICE, AND THE METAL SHEATHING HAS BEEN REMOVED FROM PATIO AND EAVES THAT WRAP AROUND THE FRONT WALKWAY. | |
01/09/2009 | INSP - FULL | Continued | Waiting on sprinkler extension estimate; looking for original plans to see if it was permitted to be built with a covered patio and no sprinkler coverage. Still need to drop sprinkler head in the SW office area. They have corrected all other violations and are working toward compliance. | |
12/23/2008 | INSP - FULL | Not ready for Inspection | All violations have been corrected with the exception of the sprinklers being dropped in a room for coverage. Coverage required for covered patio ( they are looking for the approved plans as it is). Waiting on an estimate from Kazel. | |
10/29/2008 | INSP - FULL | Violation | 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. You will illuminate your emergency lighting and exit signs at all times. ( Exit sign in kitchen, in Bingo Hall exit near restrooms, Emergency lighting in womens Bingo restroom.) | |
10/29/2008 | INSP - FULL | Violation | 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. You will have your hood system cleaned from filters to roof and maintain paper work of such on the premises. |
|
10/29/2008 | INSP - FULL | Violation | 1008.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. 1008.1.9 Panic and fire exit hardware. Each door in a means of egress from a GroupAor E occupancy having an occupant load of 50 or more and any Group H occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. You will have panic hardware installed on your courtyard gates that exit to the North and West. This must be done to maintain the continuity of those exits from the Bingo Hall and the new addition room that will both be exiting into that area. |
|
10/29/2008 | INSP - FULL | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Remove extension cord in service office. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. 1) You will remove all materials covering the mesh top over the Auxillary closet in the women's restroom, so that sprinkler coverage to that area is not blocked. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. You will have your fire extinguishers inspected and maintained. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 605.1 Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. You will remove from service the extension cord that has been 'wired' to a junction box in the Bingo Office. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. You will remove the 6 plug adapter in used next to the gaming machine found in the 'addition' across from the bar. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. You will secure your CO2 containers to prevent falling. ( in bar, and in kitchen ) approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. You will maintain clearance around all Electrical panels. ( dry storage room). approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 1008.1.8.4 Bolt locks. Manually operated flush bolts or surface bolts are not permitted. You will remove your slide bolt lock from security door on inside of rear Kitchen exit. You will replace key lock cylinder on rear Kitchen exit with a thumb turn bolt. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 1008.1.2 Door swing. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons. You will remove the security door from your rear kitchen exit and cause it to swing in the direction of travel. approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 308.3.1 Open-flame cooking devices. Charcoal burners and other open-flame cooking devices shall not be operated on combustible balconies or within 10 feet (3048 mm) of combustible construction. You will move your BBQ grill out from under the combustible eaves of your courtyard and maintain 10 feet of distance from the structure at all times ( storage or in use). approved 11/21 |
|
10/29/2008 | INSP - FULL | Violation | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. 1)You must extend your sprinkler coverage to include the SERVICE OFFICE. Contact your contractor to have them draw up plans to include your service office. The plans will be submitted to Development Services Department ( 201 N Stone) for approval before any work begins. 2) You must extend your sprinkler coverage to include the COVERED PATIO AND EAVES. Contact your contractor to have them draw up plans to include these areas. The plans will be submitted to Development Services Department ( 201 N Stone) for approval before any work begins. approved 11/18/09 |