Case: T08FR04047

Parcel: 12111366A


Addresses:

4759 E SPEEDWAY BL

Inspection Status: No Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/05/2008 INSP - FULL No Violation NOTE: THE FLAMMABLE LIQUIDS CURRENTLY BEING STOCKED ARE ACTUALLY CLASS I-B DUE TO HAVING A BOILING POINT ABOVE 100 DEG. F.
11/05/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.11/05/08
10/29/2008 INSP - FULL Violation 1.) TFC 315.2 STORAGE IN SPRINKLERED BUILDINGS SHALL BE MAINTAINED 18" BELOW SPRINKLER HEAD DEFLECTORS.
10/29/2008 INSP - FULL Violation 2.) TFC 605.6 ELECTRICAL JUNCTION BOX ON SOUTH WALL OF BACK ROOM MUST HAVE A COVER PLATE INSTALLED.
10/29/2008 INSP - FULL Violation 3.) TFC 2703.1.1 THE AMOUNT OF CLASS 1-A FLAMMABLE LIQUIDS STORED IN YOUR BACK ROOM EXCEEDS THE MAXIMUN ALLOWABLE QUANTITY BY THE FIRE CODE. REFERENCE TFC 3403.3.4.1 TABLE FOR FLAMMABLE AND COMBUSTIBLE LIQUIDS IN WHOLESALE AND RETAIL SALES OCCUPANCIES.
10/29/2008 INSP - FULL Violation 4.) TFC 2703.5 HAZARD IDENTIFICATION SIGNS. NFPA 704 SIGNS FOR CLASS 1-A FLAMMABLE LIQUIDS MUST BE POSTED AT ENTRANCES TO BUILDING.
10/29/2008 INSP - FULL Violation 5.) TFC 2703.7.1 "NO SMOKING" SIGNS SHALL BE POSTED IN ROOMS OR AREAS WHERE FLAMMABLE LIQUIDS ARE STORED.