Case: T08FR04009

Parcel: 11306147B


Addresses:

3250 N CAMPBELL AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR04009

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/05/2009 INSP - FULL Approved UNABLE TO CHECK FOR STORAGE. 4 REINSPECTIONS AND 1 PHONE CALL. BUSINESS APPEARS TO BE CLOSED.
10/28/2008 INSP - FULL Correction Required DURING THE ANNUAL SPRINKLER INSPECTION AT 3250 N. CAMPBELL THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE.

1) IN THE FISH STORE A SPRINKLER HEAD LOCATED IN FRONT OF THE SOUTH REAR EXIT IS BLOCKED BY STORAGE. A CLEAR AREA OF 18 INCHES BELOW SPRINKLERS SHALL BE MAINTAINED.

2) THE SPRINKLER RISER ROOM SHALL BE AFFORDED SPRINKLER PROTECTION . ALSO THE RISER ROOM SHALL BE FREE OF ALL STORAGE FOR ACESSABILITY.

3) THE CEILING TILES IN THE FISH STORE SHALL BE REPLACED

4) THE ALARM CONTROL VALVE FOR THE WATER MOTOR GONG SHALL BE LEFT IN THE PROPER POSITION