Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2008 | INSP - FULL | Approved | ||
| 10/28/2008 | INSP - FULL | Correction Required | SUITE #105 DURING THE ANNUAL FIRE SPRINKLER INSPECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED. 1) ALL STORAGE SHALL BE LOWERED TO NO CLOSER THAN 18 INCHES BELOW A SPRINKLER HEAD DEFLECTOR. STORAGE IS BLOCKING SPRAY PATTERNS. 2) MANY SPRINKLER HEADS ARE DUST LADEN AND SHALL BE CLEANED. DO NOT USE CHEMICALS IN THE CLEANING PROCESS. |