Case: T08FR03968

Parcel: 10707007D

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR03968

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/10/2009 INSP - FULL Approved FIELD INSPECTION APPROVED BY INSP.RAMIREZ
05/28/2009 INSP - FULL Correction Required PRE-CITATION DELEATED, PERMIT SECURED W/ SUBMITTAL
10/28/2008 INSP - FULL Correction Required DURING THE ANNUAL INSPECTION OF THE FIRE PROTECTION SYSTEM, THE FOLLOWIND DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS.

1) THE FOLLOWING AREAS NEED SPRINKLER PROTECTION ADDED: THE SPRAY BOOTH, THE SECOND FLOOR BATH ROOM AND IN FRONT OF THE SECOND FLOOR BATHROOM.

2) THE WATER MOTOR GONG DID NOT RING AND IS IN NEED OF REPAIR

3) 16 PENDANT SPRINKLER HEADS IN THE NORTH WORKSHOP NEED TO TURNED TO UPRIGHTS.

NOTE: THE ADDITION OF SPRINKLERS WILL REQUIRE SUBMITTALS AND A PERMIT BY A QUALIFIED SPRINKLER CONTRACTOR.