Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/10/2009 | INSP - FULL | Approved | FIELD INSPECTION APPROVED BY INSP.RAMIREZ | |
05/28/2009 | INSP - FULL | Correction Required | PRE-CITATION DELEATED, PERMIT SECURED W/ SUBMITTAL | |
10/28/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL INSPECTION OF THE FIRE PROTECTION SYSTEM, THE FOLLOWIND DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. 1) THE FOLLOWING AREAS NEED SPRINKLER PROTECTION ADDED: THE SPRAY BOOTH, THE SECOND FLOOR BATH ROOM AND IN FRONT OF THE SECOND FLOOR BATHROOM. 2) THE WATER MOTOR GONG DID NOT RING AND IS IN NEED OF REPAIR 3) 16 PENDANT SPRINKLER HEADS IN THE NORTH WORKSHOP NEED TO TURNED TO UPRIGHTS. NOTE: THE ADDITION OF SPRINKLERS WILL REQUIRE SUBMITTALS AND A PERMIT BY A QUALIFIED SPRINKLER CONTRACTOR. |