Case: T08FR03912

Parcel: 10706002K


Addresses:

902 W MIRACLE MILE


Inspection Status: Approved

Inspection History: INSP - AST

Case Number - T08FR03912

Inspection Description - INSP - AST

Inspection Status - Approved

Date Description Inspector Results Comments
12/31/2008 INSP - AST Approved Bollards repaired
12/31/2008 INSP - AST Approved Signs replaced
12/31/2008 INSP - AST Approved E-stop labled
10/23/2008 INSP - AST Correction Required 2207.5.3 Vehicle impact protection. Vehicle impact protection
for LP-gas storage containers, pumps and dispensers
shall be provided in accordance with Section 2206.4.
-Replace the damaged bollards.
10/23/2008 INSP - AST Correction Required 3807.2 Smoking and other sources of ignition. “No Smoking”
signs complying with Section 310 shall be posted when
required by the fire code official. Smoking within 25 feet (7620
mm) of a point of transfer.
-Please replace the faded warning signs
10/23/2008 INSP - AST Correction Required 2203.2 Emergency disconnect switches. An approved,
clearly identified and readily accessible emergency disconnect
switch shall be provided at an approved location, to stop the
transfer of fuel to the fuel dispensers in the event of a fuel spill
or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480
mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers.
Such devices shall be distinctly labeled as: EMERGENCY
PROPANE SHUTOFF. Signs shall be provided in
approved locations.
-Properly lable the emergency stop