Case: T08FR03899

Parcel: 13506136C


Addresses:

2544 S KOLB RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR03899

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/20/2008 INSP - FULL Approved All violations have been corrected.
10/22/2008 INSP - FULL Violation IFC 1004.3 Posting of occupant load. Every room or space that is an assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.
10/22/2008 INSP - FULL Violation 605.1 Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used. You will have a licensed electrician repair or replace the cords to:
1) the lights in the soup buffet bar
2) the steamer in the kitchen
Both items have been red tagged as a hazard and shall not be used until properly repaired and tag is removed upon reinspection by the fire inspector.
10/22/2008 INSP - FULL Violation IFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. You will remove from use any adapters that are not approved.
1) connecting extension cord to two power strips under soup buffet bar
2) in kitchen dishwashing area, connecting radio and 4 other appliances
10/22/2008 INSP - FULL Violation 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. You will remove any extension cords in the business.
1) At soup buffet bar; connecting power strips and cube adapter to a wall outlet.
10/22/2008 INSP - FULL Violation 605.6 Unapproved conditions. Approved covers shall be provided for all switch and electrical outlet boxes. You will place a faceplate over open outlet near S Exit doors and lighting controls.
10/22/2008 INSP - FULL Violation 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. You will connect your power strips directly to a wall outlet:
1) 2 powerstrips under soup buffet bar
10/22/2008 INSP - FULL Violation IFC 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained. You will replace the missing ceiling tile over your ventilation duct work found in the stock room between the kitchen and dining areas.
10/22/2008 INSP - FULL Violation 906.2 General requirements. Portable fire extinguishers shall be maintained in accordance with this section and NFPA 10. You will maintain your fire extinguisher or remove it.
1) found between Pepsi cooler and wall in dining area.
10/22/2008 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. You will have:
1) caps replaced over nozzles over deep fat fryer and wok in kitchen.
2) escussion plate must be placed so as not to leave a gap between ceiling and plate ( over soup buffet bar).
10/22/2008 INSP - FULL Violation 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. You will remove the bolt lock on your panic hardware on rear exit from stock room.
10/22/2008 INSP - FULL Violation 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. You will cause your emergency lighting to operate over your front exit doors.
10/22/2008 INSP - FULL Violation 1003.5 Elevation change. Where changes in elevation of less than 12 inches (305 mm) exist in the means of egress, sloped surfaces shall be used.
A step is permitted in aisles serving seating that has a difference in elevation less than 12 inches (305 mm) at locations not required to be accessible by Chapter 11 of the International Building Code, provided that the risers and treads comply with Section 1025.11 and
the aisle is provided with a handrail complying with Section 1025.13.
1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element other than a means of egress component as specified in this chapter.
Your exiting from the stage area is not in compiance with the continuity of an exit. In order to comply you can:
1)Remove the booth seating on your stage area
or
2)Provide an accessable stair and hand rail to exit from stage area.
10/22/2008 INSP - FULL Violation 3003.5.3 Securing compressed gas containers, cylinders and tanks. Compressed gas containers, cylinders and tanks shall be secured to prevent falling caused by contact, vibration or seismic activity. You will secure all compressed gas tanks or cylinders in business.
1) 3 CO2 tanks next to soda dispenser.