Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR03874

Parcel: 12801005H

Inspection Status: Correction Required

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T08FR03874

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
10/21/2008 VIOL - BUILDING SVCS & SYSTEMS Correction Required Blocked electrical panel:
TFC 605.3 - A working space of not less than 30 inches in width, 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment.

_____ Clear area around electrical panels and transformer.