Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/22/2008 | INSP - FULL | Approved | ||
| 10/21/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE ALARM INSPECTION THE FOLLOWING DEFICIENCY WAS FOUND AND IS IN NEED OF CORRECTION WITH IN 30 DAYS: 1) THE DUCT DETECTORS DID NOT SHUT DOWN THE AIR HANDLER SYSTEMS IN ALARM ACTIVATION. REPAIRS SHALL BE MADE WITHIN 30 DAYS AND A COPY OF THE CORRECTION INVOICE SHALL BE PROVIDED THIS OFFICE. ALSO PLEASE ENCLOSE A COPY OF THE ANNUAL SPRINKLER INSPECTION REPORT |