Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/29/2009 | INSP - FULL | Approved | PRE-CITATION DELETED, CORRECTION REPORT TO SYSTEMS | |
| 05/27/2009 | INSP - FULL | Correction Required | PRE-CITATION SENT 5-27-09 | |
| 03/16/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 11-10=-2008 FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 1615 E. 2ND. ST. IF CORRECTED HAVE THE CONTRACTOR OF RECORE FORWARD THEIR REPORT. |
|
| 11/10/2008 | INSP - FULL | Correction Required | DURING THE ANNUAL FIRE SPRINKLER INSPECTION (11-5-08) THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITH IN 30 DAYS. A COPY OF THE REPAIR MANIFEST SHALL BE FORWARDED TO THIS OFFICE. 1) THE SPRINKLER RISER IS DUE FOR THE 5 YEAR INTERNAL INSPECTION 2) THE SPARE HEAD BOX NEEDS THE WRENCH FOR THE SPRINKLERS 3) THE WATER MOTOR GONG DID NOT STOP RINGING AND THE VALVE WAS LEFT IN THE OFF POSITION. THE DEVICE SHALL BE REPAIRED. 4) SPRINKLER PIPING SHALL NOT BE USED TO HANG ITEMS FROM |
|
| 10/17/2008 | INSP - FULL | Correction Required | WHEREAS THIS OFFICE DOES NOT HAVE A CURRENT REPORT OF INSPECTION, A COPY SHALL BE PROVIDED THIS OFFICE WITH IN 30 DAYS |