Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/11/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 10/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. ____Fire Alarm system due for annual inspection. ____Test all battery powered smoke detectors in bedrooms. Provide documentation upon re-inspection. |
|
| 10/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. ____Hood extinguishing system due for 6 month inspection. |
|
| 10/07/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Fire extinguishers need annual inspection. |