Case: T08FR03553

Parcel: 126042770


Addresses:

4320 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/23/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.10/23/08.
10/07/2008 INSP - FULL Violation 1.) TFC 2703.1.1 THE AMOUNT OF CLASS 1A FLAMMABLE LIQUID CURRENTLY STOCKED IN YOUR WAREHOUSE AREA EXCEEDS THE MAXIMUM ALLOWABLE QUANTITY BY THE FIRE CODE. REDUCE THE QUANTITY OF CLASS 1A FLAMMABLE LIQUID STORAGE AND/OR UTILIZE FLAMMABLE LIQUID CABINETS OR CUNSTRUCT A HAZARDOUS MATERIALS CONTROL AREA.
10/07/2008 INSP - FULL Violation 2.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER MOUNTED AT THE ENTRANCE OF THE TRAINING ROOM IS PAST DUE FOR ANNUAL INSPECTION.
10/07/2008 INSP - FULL Violation 3.) TFC 605.6 THE ELECTRICAL OUTLET BY THE DOOR IN THE TRAINING ROOM MUST HAVE COVER PLATE INSTALLED.
10/07/2008 INSP - FULL Violation 4.) TFC 605.3 A 30" WORKING SPACE MUST BE PROVIDED IN FRONT OF THE ELECTRICAL BREAKER PANEL BY REAL ROLLUP DOOR.
10/07/2008 INSP - FULL Violation 5.) TFC 315.2.1 STORAGE SHALL BE MAINTAINED AT A MINIMUM FOR 18" BELOW SPRINKLER HEADS ON STORAGE SHELVES.
10/07/2008 INSP - FULL Violation 6.) TFC 504.2 THE DOUBLE DOORS IN THE SHELF STORAGE ROOM MUST HAVE A SIGN ON THE EXTERIOR SIDE STATING "THIS DOOR BLOCKED". THE LETTERS MUST BE 6' HIGH WITH A STROKE WIDTH OF AT LEAST .75 INCHES WIDE.
10/07/2008 INSP - FULL Violation 7.0 TFC 605.6 THE OPEN WIRE SPLICE ON THE EAST WALL OF THE MIXING ROOM BY SHELVING NEAR THE REAR DOOR MUST BE ENCLOSED IN A JUNCTION BOX.
10/07/2008 INSP - FULL Violation NOTE: THE SPRINKLER SYSTEM HAS A CURRENT INSPECTION TAG.