Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR03552
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/21/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.10/21/08. | |
10/06/2008 | INSP - FULL | Violation | 1.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT ABOVE FRONT DOOR MUST BE SERVICED/REPAIRED TO ILLUMINATE PROPERLY. | |
10/06/2008 | INSP - FULL | Violation | 2.) TFC 1011.4 THE INTERNALLY ILLUMINATED EXIT SIGN MUST BE ILLUMINATED AT ALL TIMES. REPAIR SIGN SO THAT IT ILLUMNATES. | |
10/06/2008 | INSP - FULL | Violation | 3.) TFC 605.4 THE CUBE TYPE ELECTRICAL ADAPTER AT THE CEILING ABOVE THE MAIN EXIT DOOR IS NOT PERMITTED BY THE FIRE CODE. | |
10/06/2008 | INSP - FULL | Violation | 4.) TFC 3003.5.3 THE COMPRESSED GAS CYLINDERS IN KITCHEN MUST BE SECURED TO PREVENT FALLING. | |
10/06/2008 | INSP - FULL | Violation | 5.) TFC 901.6.2 THE BUILDING'S SPRINKLER SYSTEM IS PAST DUE FOR ANNUAL INSPECTION. HAVE THE SYSTEM INSPECTED AND CORRECT ANY NOTED DISCREPANCIES. |