Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/17/2008 | VIOL - FLAMMABLE LIQUIDS | Approved | Vents are installed | |
| 11/17/2008 | VIOL - FLAMMABLE LIQUIDS | Approved | Bollards have been installed IAW the 2006 IFC | |
| 10/06/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.The venting shall be installed and maintained in accordancewith Section 4.2.5.2 of NFPA 30. |
|
| 10/06/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.9.6.5 Vehicle impact protection. Where protected above-ground tanks, piping, electrical conduit or dispensers are subject to vehicular impact, they shall be protected therefrom, either by having the impact protection incorporated into the system design in compliance with the impact test protocol of UL 2085, or by meeting the provisions of Section 312, or where necessary, a combination of both. Where guard posts or other approved barriers are provided, they shall be independent of each above-ground tank. |