Case: T08FR03546

Parcel: 11308279D

Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Date Description Inspector Results Comments
11/17/2008 VIOL - FLAMMABLE LIQUIDS Approved Vents are installed
11/17/2008 VIOL - FLAMMABLE LIQUIDS Approved Bollards have been installed IAW the 2006 IFC
10/06/2008 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.4 Emergency venting. Stationary,
above-ground tanks shall be equipped with additional
venting that will relieve excessive internal pressure
caused by exposure to fires.The venting shall be installed and maintained in accordancewith Section 4.2.5.2 of NFPA 30.
10/06/2008 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.9.6.5 Vehicle impact protection. Where protected
above-ground tanks, piping, electrical conduit
or dispensers are subject to vehicular impact, they
shall be protected therefrom, either by having the
impact protection incorporated into the system design
in compliance with the impact test protocol of UL
2085, or by meeting the provisions of Section 312, or
where necessary, a combination of both. Where guard
posts or other approved barriers are provided, they
shall be independent of each above-ground tank.