Case: T08FR03546

Parcel: 11308279D

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
11/17/2008 VIOL - PRECAUTION AGAINST FIRE Approved
10/06/2008 VIOL - PRECAUTION AGAINST FIRE Correction Required 312.2 Posts. Guard posts shall comply with all of the following
requirements:
1. Constructed of steel not less than 4 inches (102 mm) in
diameter and concrete filled.
2. Spaced not more than 4 feet (1219 mm) between posts on
center.
3. Set not less than 3 feet (914 mm) deep in a concrete footing
of not less than a 15-inch (381 mm) diameter.
4. Set with the top of the posts not less than 3 feet (914 mm)
above ground.
5. Located not less than 3 feet (914 mm) from the protected
object.