Inspection History Details
Inspection Status: Violation
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/08/2009 | INSP - FULL | Violation | Problem: IFC IFC 1008.1.8.3 Locks and latches. Locks and latches shall be permitted to prevent operation of doors where any of the following exists: In buildings in occupancy Group A having an occupant load of 300 or less, Groups B, F,Mand S, and in places of religious worship, the main exterior door or doors are permitted to be equipped with key-operated locking devices from the egress side provided: A readily visible durable sign is posted on the egress side on or adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. CORRECTION: YOU WILL POST THE ABOVE MENTIONED SIGN ABOVE YOUR MAIN EXIT DOOR. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: YOUR ORGAN IS BLOCKING YOUR EXIT. 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice. CORRECTION: MOVE THE ORGAN SO THAT THE EXIT DOOR HAS A CLEAR PATH OF TRAVEL TO IT AND MAINTAIN THAT PATHS WIDTH AS THE SAME AS THE DOORS WIDTH. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: FIRE EXTINGUISHER IS SITTING ON COUNTER. 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. PLACE YOUR EXTINGUISHER ON A WALL MOUNTED BRACKET IN A CONSPICIOUS PLACE IN THE TRAVEL OF EXIT. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: YOU HAVE A OUTLET IN YOUR ATTIC WITH NO COVER. 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. CORRECTION: PLACE THE REQUIRED COVER OVER YOUR OUTLET. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: YOUR FIRE EXTINGUISHER HAS NOT BEEN INSPECTED THIS PAST YEAR. 907.20.5 Maintenance, inspection and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the fire code official. CORRECTION: YOU WILL HAVE YOUR EXTINGUISHER SERVICED BY A QUALIFIED PROFESSIONAL. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: SHELF IN CLOSET IS BLOCKING SPRINKLER FLOW. 903.3.3 Obstructed locations. Automatic sprinklers shall be installed with due regard to obstructions that will delay activation or obstruct the water distribution pattern. Automatic sprinklers shall be installed in or under covered kiosks, displays, booths, concession stands, or equipment that exceeds 4 feet (1219 mm) in width. Not less than a 3-foot (914 mm) clearance shall be maintained between automatic sprinklers and the top of piles of combustible fibers. CORRECTION: REMOVE SHELF OR DROP A SPRINKLER HEAD BELOW IT. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: THERE ARE HOLES IN THE WALL OF YOUR CLOSET. 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained. CORRECTION: REPAIR HOLES OR USE FIRE RESISTANT FOAM TO FILL HOLES IN WALL. |
|
| 12/11/2008 | INSP - FULL | Violation | PROBLEM: YOUR EMERGENCY LIGHTS 1) FELLOWSHIP HALL 2) SANCTUARY NEAR E. EXIT ARE NOT WORKING. 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. CORRECTION: YOU WILL CAUSE YOUR EMERGENCY LIGHTING TO WORK APPROPRIATLY. |
|
| 12/11/2008 | INSP - FULL | Violation | Problem: Your main exit door and your fellowhip hall doors 1) do not swing in the direction of egress, Your 2nd exit from the worship hall has a lock in addition to the panic hardware. 1008.1.9 Panic and fire exit hardware. Each door in a means of egress from a Group A occupancy having an occupant load of 50 or more shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. (exception - 1008.1.8.3 states places of religious worship and having an occupant load of less than 300 may have a key operated lock on the egress side, providing you place a sign adjacent to the door that states " These doors to remain unlocked while the building is occupied" 1008.1.2 Doors shall swing in the direction of egress travel where serving an occupant load of 50 persons or more. CORRECTION: YOU WILL:1) HAVE YOUR DOORS MADE TO SWING OUT 2) YOU WILL PLACE A SIGN ABOVE THE MAIN EXIT STATING " THESE DOORS TO REMAIN UNLOCKED WHILE THE BUILDING IS OCCUPIED" 3) YOU WILL REMOVE THE THUMBOLT LOCK ON YOUR SECOND EXIT THAT ALREADY HAS PANIC HARDWARE INSTALLED. |
|
| 10/06/2008 | INSP - FULL | Correction Required | sprinkler test full inspection required |