Case: T08FR03471

Parcel: 11516019S


Addresses:

1375 W GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR03471

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
06/12/2009 INSP - FULL Approved ALL ITEMS CORRECTED BY FIELD INSPECTIONS
04/27/2009 INSP - FULL Correction Required ALL DEFICIENCIES CORRECTED WITH THE EXCEPTION OF THE FOLLOWING ITEMS. PLEASE HAVE THEM CORRECTED WITH IN 30 DAYS AND A COPY OF THE REPAIR MANIFEST SENT TO FIRE PREVENTION.

1) PROVIDE A HYDRAULIC CALCULATION PLATE AT THE RISER

2) PROVIDE SIGNAGE FOR THE SPRINKLER RISER ROOM DOOR

3) PROVIDE VERIFICATION FROM A SPRINKLER CONTRACTOR THAT ALL SPRINKLERS IN THE KITCHEN ARE OF THE SAME STANDARD
03/06/2009 INSP - FULL Correction Required SECOND NOTICE
THIS OFFICE HAS NOT RECEIVED A NOTICE OF COMPLIANCE FOR THE NOTICE DATED 10-13-08, AND OUR CONVERSATION ON 12-22-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 1375 W. GRANT. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT.
10/13/2008 INSP - FULL Correction Required DURING THE RECENT ANNUAL INSPECTION OF THE FIRE PROTECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE CORRECTION REPORT SHALL BE FORWARDED TO THIS OFFICE. A COPY OF THE ANNUAL FIRE ALARM REPORT SHALL BE FORWARDED ALSO.

1) A HYDRAULIC CALCULATION PLATE SHALL BE AT THE SPRINKLER RISER

2) THE SPRINKLER HEADS IN THE LOBBY ARE DUST LOADED AND NEED TO BE CLEANED


3) 1ST. FLOOR OFFICE AREA, THE FLEX DUCT WORK IS OBSTRUCTING SPRINKLER SPRAY PATTERN.(PROJECTION CLOSET.

4) CORRECT SPRINKLER COVERAGE SHALL BE BOARD ROOM, IN THE CORNER BY THE COFFEE BAR.

5) FITNESS ROOM-DUE TO A REMODEL A SPRINKLER HEAD EXCEEDS THE ALLOWABLE DISTANCE OFF THE WEST WALL, ONE SHALL BE ADDED.

6) SECOND FLOOR, NORTH STORE ROOM, PROVIDE THE HEAD GUARD FOR THE SPRINKLER

7) 5TH. FLOOR STAIRS - REPLACE THE NOT ON THE HANDLE FOR THE FIRE HOSE VALVE.

8) ALL SPRINKLER HEADS IN THE KITCHEN SHALL BE THE SAME




4)
10/01/2008 INSP - FULL Correction Required sprinkler test full inspection required