Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR03471
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2009 | INSP - FULL | Approved | ALL ITEMS CORRECTED BY FIELD INSPECTIONS | |
| 04/27/2009 | INSP - FULL | Correction Required | ALL DEFICIENCIES CORRECTED WITH THE EXCEPTION OF THE FOLLOWING ITEMS. PLEASE HAVE THEM CORRECTED WITH IN 30 DAYS AND A COPY OF THE REPAIR MANIFEST SENT TO FIRE PREVENTION. 1) PROVIDE A HYDRAULIC CALCULATION PLATE AT THE RISER 2) PROVIDE SIGNAGE FOR THE SPRINKLER RISER ROOM DOOR 3) PROVIDE VERIFICATION FROM A SPRINKLER CONTRACTOR THAT ALL SPRINKLERS IN THE KITCHEN ARE OF THE SAME STANDARD |
|
| 03/06/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A NOTICE OF COMPLIANCE FOR THE NOTICE DATED 10-13-08, AND OUR CONVERSATION ON 12-22-08, FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 1375 W. GRANT. IF CORRECTED, HAVE THE CONTRACTOR OF RECORD FORWARD THEIR REPORT. |
|
| 10/13/2008 | INSP - FULL | Correction Required | DURING THE RECENT ANNUAL INSPECTION OF THE FIRE PROTECTION THE FOLLOWING DEFICIENCIES WERE FOUND AND SHALL BE CORRECTED WITHIN 30 DAYS. A COPY OF THE CORRECTION REPORT SHALL BE FORWARDED TO THIS OFFICE. A COPY OF THE ANNUAL FIRE ALARM REPORT SHALL BE FORWARDED ALSO. 1) A HYDRAULIC CALCULATION PLATE SHALL BE AT THE SPRINKLER RISER 2) THE SPRINKLER HEADS IN THE LOBBY ARE DUST LOADED AND NEED TO BE CLEANED 3) 1ST. FLOOR OFFICE AREA, THE FLEX DUCT WORK IS OBSTRUCTING SPRINKLER SPRAY PATTERN.(PROJECTION CLOSET. 4) CORRECT SPRINKLER COVERAGE SHALL BE BOARD ROOM, IN THE CORNER BY THE COFFEE BAR. 5) FITNESS ROOM-DUE TO A REMODEL A SPRINKLER HEAD EXCEEDS THE ALLOWABLE DISTANCE OFF THE WEST WALL, ONE SHALL BE ADDED. 6) SECOND FLOOR, NORTH STORE ROOM, PROVIDE THE HEAD GUARD FOR THE SPRINKLER 7) 5TH. FLOOR STAIRS - REPLACE THE NOT ON THE HANDLE FOR THE FIRE HOSE VALVE. 8) ALL SPRINKLER HEADS IN THE KITCHEN SHALL BE THE SAME 4) |
|
| 10/01/2008 | INSP - FULL | Correction Required | sprinkler test full inspection required |