Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2009 | INSP - FULL | Approved | All violations have been corrected. | |
| 12/12/2008 | INSP - FULL | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. PROBLEM: OPEN WIRING SPLICE NOT IN JUNCTION BOX. CORRECTION: PLACE THE OPEN WIRING SPLICE (IN THE PRESCHOOL 1 BUILDING ON THE CEILING) IN A JUNCTION BOX. |
|
| 12/12/2008 | INSP - FULL | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. PROBLEM: YOUR FIRE EXTINGUISHERS HAVE NOT BEEN SERVICED IN THE PAST YEAR. CORRECTION: HAVE YOUR FIRE EXTINGUISHERS SERVICED BY A QUALIFIED PROFESSIONAL. |
|
| 12/12/2008 | INSP - FULL | Violation | 1024.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way PROBLEM: YOUR EXIT FROM THE ALTER IS BLOCKED ON THE OUTSIDE BY SHRUBS. CORRECTION: CUT BACK THE SHRUBS IN EXIT PATH. |
|
| 12/12/2008 | INSP - FULL | Violation | 907.20.1 Maintenance required. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection or any other feature is required for compliance with the provisions of this code, such device, equipment, system, condition, arrangement, level of protection or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as directed by the fire code official. PROBLEM: YOUR SPRINKLER SYSTEM HAS NOT BEEN SERVICED, INSPECTED, OR MAINTAINED. CORRECTION: YOU WILL HAVE YOUR SPRINKLER SYSTEM SERVICED BY A QUALIFIED PROFESSIONAL AND REPLACE THE 2 BROKEN GUAGES. |
|
| 12/12/2008 | INSP - FULL | Violation | 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur. PROBLEM: STORAGE IN HOT WATER HEATER/UTILITY ROOM IS TOO CLOSE TO HEAT SOURCE. CORRECTION: MOVE ALL COMBUSTIBLES AT LEAST THREE FEET BACK FROM A HEAT SOURCE. |
|
| 12/12/2008 | INSP - FULL | Violation | 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice. PROBLEM: BLOCKED EXIT IN PRESCHOOL ROOM STORAGE AREA. CORRECTION: REMOVE OBJECTS BLOCKING THE DOOR IN THIS ROOM. |
|
| 10/01/2008 | INSP - FULL | Correction Required | sprinkler report- needs full inspection. |