Case: T08FR03427

Parcel: 134041900

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
01/09/2009 INSP - FULL Approved All violations have been corrected.
12/12/2008 INSP - FULL Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
PROBLEM: OPEN WIRING SPLICE NOT IN JUNCTION BOX.
CORRECTION: PLACE THE OPEN WIRING SPLICE (IN THE PRESCHOOL 1 BUILDING ON THE CEILING) IN A JUNCTION BOX.
12/12/2008 INSP - FULL Violation 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10.
PROBLEM: YOUR FIRE EXTINGUISHERS HAVE NOT BEEN SERVICED IN THE PAST YEAR.
CORRECTION: HAVE YOUR FIRE EXTINGUISHERS SERVICED BY A QUALIFIED PROFESSIONAL.
12/12/2008 INSP - FULL Violation 1024.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way
PROBLEM: YOUR EXIT FROM THE ALTER IS BLOCKED ON THE OUTSIDE BY SHRUBS.
CORRECTION: CUT BACK THE SHRUBS IN EXIT PATH.
12/12/2008 INSP - FULL Violation 907.20.1 Maintenance required. Whenever or wherever any device, equipment, system, condition, arrangement, level of protection or any other feature is required for compliance with the provisions of this code, such device, equipment, system, condition, arrangement, level of protection or other feature shall thereafter be continuously maintained in accordance with applicable NFPA requirements or as
directed by the fire code official.
PROBLEM: YOUR SPRINKLER SYSTEM HAS NOT BEEN SERVICED, INSPECTED, OR MAINTAINED.
CORRECTION: YOU WILL HAVE YOUR SPRINKLER SYSTEM SERVICED BY A QUALIFIED PROFESSIONAL AND REPLACE THE 2 BROKEN GUAGES.
12/12/2008 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials in buildings shall be orderly. Storage shall be separated from heaters or heating devices by distance or shielding so that ignition cannot occur.
PROBLEM: STORAGE IN HOT WATER HEATER/UTILITY ROOM IS TOO CLOSE TO HEAT SOURCE.
CORRECTION: MOVE ALL COMBUSTIBLES AT LEAST THREE FEET BACK FROM A HEAT SOURCE.
12/12/2008 INSP - FULL Violation 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice.
PROBLEM: BLOCKED EXIT IN PRESCHOOL ROOM STORAGE AREA.
CORRECTION: REMOVE OBJECTS BLOCKING THE DOOR IN THIS ROOM.
10/01/2008 INSP - FULL Correction Required sprinkler report- needs full inspection.