Case: T08FR03411

Parcel: 12415004A


Addresses:

610 S PARK AV

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
06/04/2009 INSP - FULL Approved Sprinkler system tested and taged.
02/04/2009 INSP - FULL Violation
02/04/2009 INSP - FULL Violation 315.2 Storage in buildings. Storage of combustible materials
in buildings shall be orderly. Storage shall be separated from
heaters or heating devices by distance or shielding so that ignition
cannot occur.
315.2.1 Ceiling clearance. Storage shall be maintained 2
feet (610 mm) or more below the ceiling in nonsprinklered
areas of buildings or a minimum of 18 inches (457 mm) below
sprinkler head deflectors in sprinklered areas of buildings.
315.2.2 Means of egress. Combustible materials shall not
be stored in exits or exit enclosures.
315.2.3 Equipment rooms. Combustible material shall not
be stored in boiler rooms, mechanical rooms or electrical
equipment rooms.
02/04/2009 INSP - FULL Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an operative
condition at all times, and shall be replaced or repaired
where defective. Nonrequired fire protection systems and
equipment shall be inspected, tested and maintained or removed.
02/04/2009 INSP - FULL Violation ings, nor shall such cords be subject to environmental damage
or physical impact. Extension cords shall be used only with
portable appliances.
605.5.1 Power supply. Extension cords shall be plugged directly
into an approved receptacle, power tap or multiplug
adapter and, except for approved multiplug extension cords,
shall serve only one portable appliance.
02/04/2009 INSP - FULL Violation 605.3Working space and clearance. A working space of not
less than 30 inches (762 mm) in width, 36 inches (914 mm) in
depth and 78 inches (1981 mm) in height shall be provided in
front of electrical service equipment. Where the electrical service
equipment is wider than 30 inches (762 mm), the working
space shall not be less than the width of the equipment. No storage
of any materials shall be located within the designated
working space.
10/01/2008 INSP - FULL Correction Required sprinkler report- needs full inspection.