Case: T08FR03196

Parcel: 124040110


Addresses:

1435 E 2ND ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
10/17/2008 VIOL - MEANS OF EGRESS Approved
09/26/2008 VIOL - MEANS OF EGRESS Violation 1027.3 Exit sign illumination. Exit signs shall be internally or
externally illuminated.
1027.4 Power source. Where emergency illumination is
required in Section 1027.5, exit signs shall be visible under
emergency illumination conditions.

____Repair all inoperable Exit signs:
____Smoking patio Exit sign.
____Hallway Exit sign near bedroom #25.
____Exit sign in piano room.
____Exit sign above foyer entrance door.
09/26/2008 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system...

____Repair emergency lighting unit in hallway, 1st floor.
09/26/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

____Remove both keyed deadbolts from Exit door near House Directors room. One thumb-turn deadbolt allowed.