Case: T08FR03174

Parcel: 14115355B


Addresses:

8100 S HOUGHTON RD


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T08FR03174

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
10/16/2008 VIOL - MOTOR FUEL DISPENSING Approved
09/26/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

· Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
09/26/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2 Equipment maintenance and inspection. Motor fuel-dispensing facility equipment shall be maintained in proper working order at all times.

· Replace all cracked and damaged hoses.
· # 8 hose frayed, replace immediately.
· # 10 hose frayed, replace immediately.
· # 2 hose becoming worn, monitor wear.
· # 5 hose becoming worn, monitor wear.
09/26/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2204.2 Attended self-service motor fuel-dispensing facilities.
Attended self-service motor fuel-dispensing facilities shall have at least one qualified attendant on duty while the facility is open for business. The attendant's primary function shall be to supervise, observe and control the dispensing of fuel. The attendant shall control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers