Inspection History Details
Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T08FR03137
Inspection Description - INSP - FULL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/10/2009 | INSP - FULL | Correction Required | SECOND NOTICE THIS OFFICE HAS NOT RECEIVED A REPORT OF COMPLIANCE FOR THE NOTICE DATED 7/6/2009 FOR THE ABOVE LISTED DEFICIENCIES CONCERNING THE FIRE PROTECTION SYSTEM AT 4001 E. SPEEDWAY. IF CORRECTED HAVE THE CONTRACTOR FORWARD THEIR REPORT. THANK YOU. |
|
| 07/06/2009 | INSP - FULL | Correction Required | THE ANNUAL SPRINKLER REPORT CONTAINED THE FOLLOWING DEFICIENCIES, PLEASE FORWARD A CORRECTION REPORT WITH IN 30 DAYS. 1) PROVIDE IDENTIFICATION SIGN AT THE INSPECTORS TEST 2) REPLACE THE FIRE DEPT. COUPLING THAT HAS THE MISSING LUG 3) REPLACE THE GASKETS AT THE FIRE DEPT. CONNECTION 4) PROVIDE 155 DEGREE QUICK RESPONSE PENDANT HEADS AND A 155 DEGREE SIDEWALL QUICK RESPONSE HEAD TO THE SPARE HEAD BOX. 5) PRESSURE GUAGES TAT ARE OVER FIVE YEADS OLD SHALL BE REPLACED OR RECALIBRATED 6) PROVIDE LOCK AND CHAIN FOR THE CONTROL VALVE 7) PROVIDE 5 YEAR INTERNAL VALVE INSPECTION AT THE RISER 7) INSULATION SHALL NOT BLOCK THE SPRAY PATTERN OF SPRINKLERS 8) A BAFFEL MAY BE PROVIDED BETWEEN THE TWO SPRINKLER HEADS, NORTH EAST SHOP EXIT DOOR, THEY ARE TO CLOSE TOGEATHER |
|
| 05/14/2009 | INSP - FULL | Correction Required | FIRE PROTECTION SYSTEMS ARE REQUIRED TO BE INSPECTED AND TESTED ON AN ANNUAL BASIS. THIS PROCEDURE POSSIBLY HAS BEEN ACOMPLISHED BUT THIS OFFICE DOES NOT HAVE ON FILE A COPY OF A CURRENT REPORT. PLEASE FORWARD WITH IN 30 DAYS THE REQUESTED INFORMATION. | |
| 09/25/2008 | INSP - FULL | Correction Required | sprinkler test full inspection required |