Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR03136
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/04/2008 | INSP - FULL | Approved | ||
09/25/2008 | INSP - FULL | Violation | 1). Currently no certificate of cleaning was noticed during inspection. Hood system and vents shall be cleaned and invoice describing work completed shall be submitted for compliance. 904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. Please obtain records of cleaning. 2), Please ensure all extension cords are used for permanent wiring. IFC 605.1 This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 10-8-08. A re-inspection shall be conducted at that time to ensure compliance |