Case: T08FR03136

Parcel: 13017149A


Addresses:

1835 S ALVERNON WY


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR03136

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/04/2008 INSP - FULL Approved
09/25/2008 INSP - FULL Violation 1). Currently no certificate of cleaning was noticed during inspection.
Hood system and vents shall be cleaned and invoice describing work completed shall be submitted for compliance.

904.11.6.3 Cleaning. Hoods, grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
Please obtain records of cleaning.

2), Please ensure all extension cords are used for permanent wiring.
IFC 605.1
This letter is to inform you that abatement of these Tucson Fire Code violations must be completed by 10-8-08.
A re-inspection shall be conducted at that time to ensure compliance