Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T08FR03031

Parcel: 12404050A


Addresses:

1535 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
10/17/2008 VIOL - FIRE PROTECTION SYSTEMS Approved
09/23/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Fire alarm due for annual inspection. Provide documentation.
____Sprinkler system due for annual inspection. Provide documentation.