Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR03011
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/03/2008 | INSP - FULL | Approved | The red tag for the salamander was removed on 10-2-08 because a hood extinguishing system nozzle was added for coverage. The fryer was removed and is no longer used. ________________________________________________ (John E. Bieg, Fire Inspector, Tucson Fire Department) ______________________________ (Captain) |
|
| 10/01/2008 | INSP - FULL | Correction Required | TFC 111.1 Order. Whenever the fire code official finds any work regulated by this code being performed in a manner contrary to the provisions of this code or in a dangerous or unsafe manner, the fire code official is authorized to issue a stop work order. _____1.Cease and desist the use of the salamander and two small fryers located in the kitchen. Hood extinguishing system nozzles shall be added to properly cover the salamander and two small fryers. The salamander and two small fryers have been red tagged until the above stated corrections have been made. |
|
| 09/23/2008 | INSP - FULL | Correction Required | Salander not protected - small hoop with fryers not protected please come stop by front desk for report |