Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE SERVICE FEATURES
Case Number - T08FR02984
Inspection Description - VIOL - FIRE SERVICE FEATURES
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/05/2008 | VIOL - FIRE SERVICE FEATURES | Approved | ALL NOTED SPRINKLER SYSTEM DEFICIENCIES WERE CORRECTED. COPY OF INSPECTION REPORT AND REPAIR RECEIPT WERE FORWARDED TO SYSTEM DESIGN. | |
| 09/19/2008 | VIOL - FIRE SERVICE FEATURES | Violation | THE FOLLOWING ITEMS WERE DEFIENCIES NOTED ON THE RECENT SPRINKLER SYSTEM INSPECTION COMPLETED BY UNITED FIRE: 1.) REPLACE MISSING SPRINKLER HEAD ESCUTCHEONS. 2.) HAVE 5 YEAR INSPECTION OF ALARM VALVE DONE. 3.) REPLACE CORODED PIPE BELOW CONTROL VALVE. 4.) REPLACE ANY MISSING SPRINKLER HEAD SPARES AND WRENCH IN BOX. |