Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2008 | VIOL - MEANS OF EGRESS | Violation | MEANS OF EGRESS ILLUMINATION 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied. TFC 1011.2 - Illumination. Exit signs shall be internally or externally illuminated. _____ Repair/replace emergency egress lighting that also illuminates externally illuminated exit signs. |