Inspection Status: Approved
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 10/06/2008 |
INSP - FULL |
|
Approved |
ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. 10/06/08 |
| 09/19/2008 |
INSP - FULL |
|
Violation |
1.) TFC 605.4 THE CUBE ADAPTER IN THE OFFICE NEEDS TO BE REMOVED FROM SERVICE. |
| 09/19/2008 |
INSP - FULL |
|
Violation |
2.) TFC 804.2 THE SOUND DEADENING FOAM MOUNTED ON THE WALL BEHIND THE AIR COMPRESSOR MUST BE REMOVED OR REPLACED WITH FLAME RETARDANT FOAM. |
| 09/19/2008 |
INSP - FULL |
|
Violation |
3.) TFC 1303.2 THE ACCUMULATION OF SAWDUST IN THE WOODSHOP AREA MUST BE COMPLETELTY REMOVED AND KEPT CLEAN ON A CONTINUING BASIS. |
| 09/19/2008 |
INSP - FULL |
|
Violation |
4.) TFC 1303.1 NO SMOKING SIGN IS REQUIRED IN THE WOODSHOP AREA. |
| 09/19/2008 |
INSP - FULL |
|
Violation |
5.) TFC 605.6 THE ELECTRICAL LIGHT SWITCH IN THE BACK ROOM NEEDS TO HAVE THE COVER PLATE SECURED PROPERLY TO COVER OPEN WIRING. |