Case: T08FR02853

Parcel: 13505149Y


Addresses:

2501 S WILMOT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR02853

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
04/07/2009 INSP - FULL Approved
04/07/2009 INSP - FULL Compliance
01/13/2009 INSP - FULL Not ready for Inspection Larry from Kazal fire called and stated that Mr. Mario Teran has initiated a sprinkler system repair work order and they would foward the information to me ASAP.
01/09/2009 INSP - FULL Not ready for Inspection Nothing has been done since my last inspection on 12/26/08. All that was done at that inspection was that the Sprinkler system had been inspected, no repairs to problems found though, and the extinguishers were inspected.
10/31/2008 INSP - FULL Violation 1011.1 Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel.
1) You will have Exit signs installed and maintained at the end of each corridor pointing to the nearest exit.
2) Where ever there is already an exit sign you will ensure that it is maintained by back up batter power and that the bulbs are working so as to cause it to light continuously.
10/31/2008 INSP - FULL Violation 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
1) You will have your emergency lighting replaced or repaired where ever it is not working.
10/31/2008 INSP - FULL Violation 703.2.3 Door operation. Swinging fire doors shall close from the full-open position and latch automatically. The door closer shall exert enough force to close and latch the door from any partially open position.
1) You will have your (NE corner Exit door, and door btwn office and residence) repaired and operating appropriatly.
10/24/2008 INSP - FULL Violation 907.20.5 Maintenance, inspection and testing. The building owner shall be responsible for ensuring that the fire and life safety systems are maintained in an operable condition at all times. Service personnel shall meet the qualification requirements of NFPA 72 for maintaining, inspecting and testing such systems. A written record shall be maintained and shall be made available to the fire code official.
1) You will have your sprinkler system tested and provide paperwork to the fire code official ( and keep a copy on the premises).
2) You will have all Fire extinguishers inspected and maintained.
10/24/2008 INSP - FULL Violation 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
1) You will replace the missing face plate on the wall switch in the south hall West of the elevator.
2) You will have your open wiring splice ( found near sprinkler pipes just N or the office reception window, and in the business office) placed in a junction box.
09/18/2008 INSP - FULL Correction Required Sprinkler test full inspection needed