Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02777

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
10/06/2008 VIOL - MEANS OF EGRESS Approved
09/15/2008 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:

____Repair emergency lighting unit over computer room door.
09/15/2008 VIOL - MEANS OF EGRESS Violation 1027.3 Exit sign illumination.

____Repair exit signs near bedroom #11 and #10.
09/15/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8.5 Unlatching. The unlatching of any door or
leaf shall not require more than one operation.

____Remove second deadbolt from kitchen Exit. Only one deadbolt lock allowed.
09/15/2008 VIOL - MEANS OF EGRESS Violation 1028.2 Reliability. Required exit accesses, exits or exit discharges
shall be continuously maintained free from obstructions
or impediments to full instant use in the case of fire or
other emergency when the areas served by such exits are occupied.

____IMMEDIATELY Remove all items blocking the Exit door. Hallway, 2nd floor
____Remove all items on floor in South hallway. 2nd floor.
09/15/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.
1008.2 Gates. Gates serving the means of egress system shall
comply with the requirements of this section. Gates used as a
component in a means of egress shall conform to the applicable
requirements for doors.

____Remove or disable the double-keyed deadbolt on courtyard gate.