Case: T08FR02776

Parcel: 12402008A


Addresses:

1801 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
12/18/2008 VIOL - MEANS OF EGRESS Approved
09/15/2008 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress.

____Test every emergency lighting unit. Provide documentation.
____Repair damaged lighting units:
____Courtyard
09/15/2008 VIOL - MEANS OF EGRESS Violation 1027.3 Exit sign illumination.
1027.4 Power source.

____Test every illuminated Exit sign. Provide documentation.
____Replace missing illuminated Exit sign near Room #207.
09/15/2008 VIOL - MEANS OF EGRESS Violation 1028.8 Panic hardware. Where panic and fire exit hardware
is installed, the panic or fire exit hardware shall be the only
locking device on the door.

____Remove deadbolt lock from main door.