Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/18/2008 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
| 09/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 906.2 General requirements. Portable fire extinguishers shall be selected, installed and maintained in accordance with this section and NFPA 10. ____Fire extinguishers need annual inspection. |
|
| 09/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 904.11.6.4 Extinguishing system service. Automatic fire-extinguishing systems shall be serviced at least every 6 months and after activation of the system. ____Commercial cooking extinguishing system needs 6 month inspection. |
|
| 09/15/2008 | VIOL - FIRE PROTECTION SYSTEMS | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. Nonrequired fire protection systems and equipment shall be inspected, tested and maintained or removed. ____Fire Alarm needs annual inspection. Provide documentation. ____Test every smoke detector in bedrooms. Provide documentation. ____Sprinkler system due for annual inspection. Provide documentation. ____Replace missing cap on Fire Dept. Connections. |