Case: T08FR02776

Parcel: 12402008A


Addresses:

1801 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
12/18/2008 VIOL - FIRE PROTECTION SYSTEMS Approved
09/15/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 906.2 General requirements. Portable fire extinguishers shall
be selected, installed and maintained in accordance with this
section and NFPA 10.

____Fire extinguishers need annual inspection.
09/15/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 904.11.6.4 Extinguishing system service. Automatic
fire-extinguishing systems shall be serviced at least
every 6 months and after activation of the system.

____Commercial cooking extinguishing system needs 6 month inspection.
09/15/2008 VIOL - FIRE PROTECTION SYSTEMS Violation 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

____Fire Alarm needs annual inspection. Provide documentation.
____Test every smoke detector in bedrooms. Provide documentation.
____Sprinkler system due for annual inspection. Provide documentation.
____Replace missing cap on Fire Dept. Connections.