Case: T08FR02776

Parcel: 12402008A


Addresses:

1801 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - FIRE SERVICE FEATURES

Date Description Inspector Results Comments
12/18/2008 VIOL - FIRE SERVICE FEATURES Approved
09/15/2008 VIOL - FIRE SERVICE FEATURES Violation 510.1 Identification. Fire protection equipment shall be identified
in an approved manner. Rooms containing controls for
air-conditioning systems, sprinkler risers and valves, or other
fire detection, suppression or control elements shall be identified
for the use of the fire department. Approved signs required
to identify fire protection equipment and equipment location,
shall be constructed of durable materials, permanently
installed and readily visible.

____Label riser room doors. "RISER ROOM"
09/15/2008 VIOL - FIRE SERVICE FEATURES Violation 508.5.4 Obstruction. Posts, fences, vehicles, growth, trash,
storage and other materials or objects shall not be placed or
kept near fire hydrants, fire department inlet connections or
fire protection system control valves in a manner thatwould
prevent such equipment or fire hydrants from being immediately
discernible. The fire department shall not be deterred
or hindered from gaining immediate access to fire protection
equipment or fire hydrants.

____Do not obstruct the Fire Dept. Connections with vehicles.