Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR02765
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/16/2008 | INSP - FULL | Approved | All corrections have been made. | |
09/12/2008 | INSP - FULL | Violation | 105.3.3 Occupancy prohibited before approval. The building or structure shall not be occupied prior to the fire code official issuing a permit that indicates that applicable provisions of this code have been met. You will go to Development Services Department and apply for your C of O. | |
09/12/2008 | INSP - FULL | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. You will remove all extension cords in use that do not have a surge protector on it. Power strips with surge protectors are a good option. I found illegal cords in use on front display wall, West wall under guitars and behind amps. | |
09/12/2008 | INSP - FULL | Violation | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. You will find a permanent power supply for your powerstrip that is plugged into the powerstrip in your amp room. | |
09/12/2008 | INSP - FULL | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. You will remove anything blocking any electrical panels. Blocked panel was found in rear storage near rear exit door. | |
09/12/2008 | INSP - FULL | Violation | 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Place a cover over opening in wall in office, and a face plate over open lightswitch socket on wall in office. | |
09/12/2008 | INSP - FULL | Violation | 906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions. Have your two fire extinguishers mounted to the wall with appropriate hangers. | |
09/12/2008 | INSP - FULL | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained. Replace missing ceiling tile in storage room next to amp room. | |
09/12/2008 | INSP - FULL | Violation | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Have your sprinkler heads in the office and in storage next to amp room placed so there is no hole in the ceilling tile above it. This is a fire resistant barrier that enables the sprinkler head to collect enough heat to activate that head in the event of a fire. | |
09/12/2008 | INSP - FULL | Violation | 1028.3 Obstructions. A means of egress shall be free from obstructions that would prevent its use, including the accumulation of snow and ice. Keep your exit hallway unblocked all the way to the exit door. Maintain the width of the door in that hallway. | |
09/12/2008 | INSP - FULL | Violation | 1008.1.8.5 Unlatching. The unlatching of any door or leaf shall not require more than one operation. Remove door anchors that hold bar in place. You may not place a lock on the exit that requires two different operations to open door for exiting. | |
09/12/2008 | INSP - FULL | Violation | 1014.4.1 Aisles in Groups B and M. In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm). Maintain 36 inches in all your merchandising aisles. |