Case: T08FR02764

Parcel: 12402034C


Addresses:

1775 E 1ST ST

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
05/13/2009 VIOL - MEANS OF EGRESS Approved
09/12/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.
1008.2 Gates. Gates serving the means of egress system shall
comply with the requirements of this section. Gates used as a
component in a means of egress shall conform to the applicable
requirements for doors.

____Remove or disable double-keyed deadbolt from West gate in courtyard. Thumb-turn deadbolt or panic hardware allowed.
09/12/2008 VIOL - MEANS OF EGRESS Violation 1008.1.2 Door swing. Egress doors shall be side-hinged
swinging. Doors shall swing in the direction of egress travel where
serving an occupant load of 50 or more persons or a Group
H occupancy.

____West gate in courtyard needs to swing outward.
09/12/2008 VIOL - MEANS OF EGRESS Violation 1027.1 General. Means of egress in existing buildings shall
comply with Sections 1003 through 1026, except as amended
in Section 1027.

____Repair emergency lighting unit in stairwell.
____Remove/Disable light switch connected to emergency lighting unit in stairwell. This lighting unit is intended for emergency use only.
09/12/2008 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress:
8. Group R-2.
Exception: Where each dwelling unit or sleeping unit
has direct access to the outside of the building at
grade.

____Emergency Lighting units required in the bedroom halls.
____Emergency Lighting units required in the Main lobby near the front and rear exit.