Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/13/2009 | VIOL - MEANS OF EGRESS | Approved | ||
| 09/12/2008 | VIOL - MEANS OF EGRESS | Violation | 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 1008.2 Gates. Gates serving the means of egress system shall comply with the requirements of this section. Gates used as a component in a means of egress shall conform to the applicable requirements for doors. ____Remove or disable double-keyed deadbolt from West gate in courtyard. Thumb-turn deadbolt or panic hardware allowed. |
|
| 09/12/2008 | VIOL - MEANS OF EGRESS | Violation | 1008.1.2 Door swing. Egress doors shall be side-hinged swinging. Doors shall swing in the direction of egress travel where serving an occupant load of 50 or more persons or a Group H occupancy. ____West gate in courtyard needs to swing outward. |
|
| 09/12/2008 | VIOL - MEANS OF EGRESS | Violation | 1027.1 General. Means of egress in existing buildings shall comply with Sections 1003 through 1026, except as amended in Section 1027. ____Repair emergency lighting unit in stairwell. ____Remove/Disable light switch connected to emergency lighting unit in stairwell. This lighting unit is intended for emergency use only. |
|
| 09/12/2008 | VIOL - MEANS OF EGRESS | Violation | 1027.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: 8. Group R-2. Exception: Where each dwelling unit or sleeping unit has direct access to the outside of the building at grade. ____Emergency Lighting units required in the bedroom halls. ____Emergency Lighting units required in the Main lobby near the front and rear exit. |