Case: T08FR02649

Parcel: 127050660


Addresses:

4766 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
09/22/2008 INSP - FULL Approved AL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
09/05/2008 INSP - FULL Violation 1.) TFC 605.4 THE MULTI-PLUG ADAPTER IN JOHN'S OFFICE NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION.
09/05/2008 INSP - FULL Violation 2.) TFC 605.4 THE MULTI-PLUG ADAPTER IN THE VERTICAL ASSEMBLY AREA NEEDS TO BE REPLACED WITH A UL/FM LISTED POWER STRIP WITH OVER CURRENT PROTECTION.
09/05/2008 INSP - FULL Violation 3.) TFC 605.5 THE EXTENSION CORD FOR SAW IN VERTICAL CUT SHOP IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
09/05/2008 INSP - FULL Violation 4.) TFC 605.5 THE EXTENSION CORD USED TO POWER THE REFRIGERATOR UPSTAIRS IN THE DRAPERY WORK ROOM IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
09/05/2008 INSP - FULL Violation 5.) TFC 605.5 THE EXTENSION CORD USED FOR SEWING MACHINE ON THE NORTH END OF BUILDING UPSTAIRS IS NOT PERMITTED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
09/05/2008 INSP - FULL Violation 6.) TFC 315.2.2 COMBUSTIBLES ARE NOT ALLOWED TO BE STORED UNDER THE EXIT STAIRWELL TO UPSTAIRS.
09/05/2008 INSP - FULL Violation 7.) TFC 1006.3 THE EMERGENCY ILLUMINATION UNIT NEAR THE EXIT DOOR ON SOUTH END OF EAST WALL IS NOT OPERATING.