Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR02647
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2008 | INSP - FULL | Approved | All violations have been corrected. | |
| 09/05/2008 | INSP - FULL | Violation | 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. You will remove ALL extension cords in use within the business - these were noted...(at front entrance ceiling, behind and on top of vegitable display, ceiling over Chase bank, over family restroom, in pharmacy office, ceiling over eggs freezer to the front of the building) | |
| 09/05/2008 | INSP - FULL | Violation | 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. You will remove all unnacceptable adapters: attaching three ext cords over the egg freezer display, anywhere else in building. | |
| 09/05/2008 | INSP - FULL | Violation | 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. You will remove all objects blocking your electrical panels and Fire Alarm Service Panel and Annunciator Panel. | |
| 09/05/2008 | INSP - FULL | Violation | 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction shall be maintained. Your ceiling tiles are a fire resistant barrier that shall be maintained. Replace missing and broken tiles ( safe room, upstairs electrical panel/ comm room, wherever tile are missing.) | |
| 09/05/2008 | INSP - FULL | Violation | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. 1.) Replace missing escussion plates in Mens Restroom at front of store, over deep fat fryer. 2.) Have your sprinkler system repaired per your last sprinkler inspection report. |
|
| 09/05/2008 | INSP - FULL | Violation | 605.4.2 Power supply. Relocatable power taps shall be directly connected to a permanently installed receptacle. You will connect multiplug power taps with over surge protectors into a separate outlet. Disconnect the two connected power strips in the pharmacy office and anywhere else they are 'piggybacked'. | |
| 09/05/2008 | INSP - FULL | Violation | 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. Where ever an extinguisher is blocked, remove obstructions : inside pharmacy entrance, in stock room between roll up loading dock doors. | |
| 09/05/2008 | INSP - FULL | Violation | 1024.6 Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. You will cover the exit sign in your rear Main Electrical Room where the exit leads to an enclosed outdoor storage area secured by a gate. Place a sign on that same door that states " Not an Exit". Leave the exit sign over the North exit door...that is the exit from this room. | |
| 09/05/2008 | INSP - FULL | Violation | 315.3.1 Storage beneath overhead projections from buildings. Combustible materials stored or displayed outside of buildings that are protected by automatic sprinklers shall not be stored or displayed under nonsprinklered eaves, canopies or other projections or overhangs. You may not stock items under your covered walkway out front because it is not sprinklered. |