Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/23/2008 | VIOL - MOTOR FUEL DISPENSING | Approved | Test documentation recieved | |
| 09/23/2008 | VIOL - MOTOR FUEL DISPENSING | Approved | Fire extinguishers have been tested and relocated. | |
| 09/08/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation. · Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer. |
|
| 09/08/2008 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill-pipe openings. · Both of your Fire Extinguishers need to be inspected. Their last yearly inspection was in 2006. In addition the extinguisher near the front door either needs to be relocated or the rack blocking it must be moved to provide a clear view of the extinguisher. |