Case: T08FR02637

Parcel: 133350040


Addresses:

8702 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
09/23/2008 VIOL - MOTOR FUEL DISPENSING Approved Test documentation recieved
09/23/2008 VIOL - MOTOR FUEL DISPENSING Approved Fire extinguishers have been tested and relocated.
09/08/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

· Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.
09/08/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.5 Fire extinguishers. Approved portable fire extinguishers complying with Section 906 with a minimum rating of 2-A:20-B:C shall be provided and located such that an extinguisher is not more than 75 feet (22 860 mm) from pumps, dispensers or storage tank fill-pipe openings.

· Both of your Fire Extinguishers need to be inspected. Their last yearly inspection was in 2006. In addition the extinguisher near the front door either needs to be relocated or the rack blocking it must be moved to provide a clear view of the extinguisher.