Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
Case Number - T08FR02636
Inspection Description - VIOL - FLAMMABLE LIQUIDS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/24/2008 | VIOL - FLAMMABLE LIQUIDS | Approved | Hoses 6,7 and 8 have been replaced and sump emptied of fluids | |
09/04/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | Section 3404.2.12.3 Existing tanks and piping. Existing underground storage tanks and piping shall be tested for leakage at the owner's or operator's expense at least every 24 months in accordance with this section. EXCEPTION: Underground storage tank systems with an approved method of detecting leaks from any component of the system. Tanks shall be emptied of flammable or combustible liquids if required tests are not completed within the specified time. When testing is required, owners or operators shall provide the fire code official with data setting forth the method of testing that is to be used and shall submit the name of a qualified individual who will conduct the test. A testing permit shall be obtained. The method of testing to be used shall consider the effects of temperature, pressure and other variables and shall establish conclusively whether the tank or piping is leaking. Pneumatic testing is prohibited. Devices used for final testing shall be capable of detecting leaks as small as 0.05 gallon per hour. Leaking piping and equipment shall not be used until repaired or replaced. The fire code official is authorized to require that the test be conducted in the code official's presence. ยท Mrs. Sandy Huff, I have a current test receipt from Compliance Management dated 03-08. The last actual test results I have on file are over five years old. Can you please send me the test results from the 03-08 tests? I would like to update the file. |
|
09/04/2008 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.10 Leak reporting. A consistent or accidental loss of liquid, or other indication of a leak from a tank system, shall be reported immediately to the fire department, the fire code official and other authorities having jurisdiction. The regular unleaded sump has fluid in it. |