Case: T08FR02548

Parcel: 13343341C


Addresses:

10290 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MOTOR FUEL DISPENSING

Case Number - T08FR02548

Inspection Description - VIOL - MOTOR FUEL DISPENSING

Inspection Status - Approved

Date Description Inspector Results Comments
09/23/2008 VIOL - MOTOR FUEL DISPENSING Approved The damaged spill buckets have been replaced.
09/23/2008 VIOL - MOTOR FUEL DISPENSING Approved All documentation of tests has been recieved
08/27/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2206.6.2.6 Spill containers. A spill container having a capacity of not less than 5 gallons (19 L) shall be provided for each fill connection. For tanks with a top fill connection, spill containers shall be noncombustible and shall be fixed to the tank and equipped with a manual drain valve that drains into the primary tank. For tanks with a remote fill connection, a portable spill container is allowed.

Repair/Replace damaged/collapsed spill buckets.
08/27/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer
08/27/2008 VIOL - MOTOR FUEL DISPENSING Correction Required 2204.2 Attended self-service motor fuel-dispensing facilities.
Attended self-service motor fuel-dispensing facilities shall have at least one qualified attendant on duty while the facility is open for business. The attendant's primary function shall be to supervise, observe and control the dispensing of fuel. The attendant shall control sources of ignition, give immediate attention to accidental spills or releases, and be prepared to use fire extinguishers.