Case: T08FR02538

Parcel: 12317252B


Addresses:

1510 N VINE AV


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T08FR02538

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2008 VIOL - MEANS OF EGRESS Approved
08/27/2008 VIOL - MEANS OF EGRESS Violation 1027.5 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premises’ electrical supply. In the event of power supply failure,
illumination shall be automatically provided from an
emergency system for the following occupancies where such
occupancies require two or more means of egress.

____Repair all damaged emergency lighting units.
____Entertainment room.
____Dining room.
____Laundry room.
____2nd floor South hall.
____Outside weight room.
____Main stairwell.
____3rd floor East hall.
____2nd floor East hall x 2.
08/27/2008 VIOL - MEANS OF EGRESS Violation 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

____Main door must open by using panic hardware only. Currently requires the press of a button to disable magnetic hardware.