Case: T08FR02519

Parcel: 12215242C


Addresses:

3444 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - AST

Case Number - T08FR02519

Inspection Description - INSP - AST

Inspection Status - Approved

Date Description Inspector Results Comments
09/18/2008 INSP - AST Approved Approved.
08/26/2008 INSP - AST Correction Required Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on August 21, 2008. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about September 9, 2008.


3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.
- Emergency venting needs to be installed.

3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
- A "Normally closed" type vent needs to be installed.