Case: T08FR02496

Parcel: 12801005H


Addresses:

5870 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - NIGHT

Case Number - T08FR02496

Inspection Description - INSP - NIGHT

Inspection Status - Approved

Date Description Inspector Results Comments
08/28/2008 INSP - NIGHT Approved A full Fire Inspection was refered to Fire Inspector Greenleaf.
08/24/2008 INSP - NIGHT Approved A Night Inspection was conducted on 8/23/2008 at approximately 2245hrs.

All theatres were showing movies and some were occupied near capacity. All exit doors were clear and unobstructed. Some emergency lighting units that were within reach and were able to be tested did not work properly. There were several lighting units that were not accessible at the time that need testing.

A full Fire Prevention Inspection need to be conducted at this location. These issues will be refered to the Team 2 South Of Broadway Captain for Inspector assignment.


________________________________________________
(John E. Bieg, Fire Inspector, Tucson Fire Department)



______________________________
(Captain)