Inspection Status: Correction Required
Inspection History: INSP - FULL
| Date |
Description |
Inspector |
Results |
Comments |
| 08/27/2008 |
INSP - FULL |
|
Correction Required |
The hood system doesn't have the proper coverage, this system has already has recieved a complaint over the same issues. The original complaint has been addressed and is being handled by systems design Ref: T08FR01940. A FPI is being schedualed as a follow up. the complaint will continue to be handled through the FPI and under the original complaint #. This complaint is closed. |
| 08/22/2008 |
INSP - FULL |
|
Correction Required |
Suppression system report lists griddles not covered by hood, nor any protection on salamander. (Copy of report attached in complaint log.) |