Case: T08FR02487

Parcel: 110120960


Addresses:

5301 E GRANT RD


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR02487

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/11/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
08/21/2008 INSP - FULL Violation AREAS INSPECTED: FAST TRACK BUILDING AND EDUCATION BUILDING.
FAST TRACK BUILDING:
1.)TFC 703.1.1 THE CEILING TILE IN THE I/S CLOSET HAS HOLES AROUND CABLES THAT NEED TO BE SEALED TO PROVIDE REQUIRED FIREBLOCKING AND DRAFTSTOPPING.
08/21/2008 INSP - FULL Violation EDUCATION BUILDING:
1.) TFC 605.5 THE EXTENSION CORD USED TO POWER THE REFRIGERATOR IN THE PLUMBING SHOP IS NOT ALLOWED TO BE A SUBSTITUTE FOR PERMANENT WIRING.
08/21/2008 INSP - FULL Violation 2.) TFC 3003.5.3 THE COMPRESSED GAS CYLINDERS IN THE PLUMBING SHOP NEED TO BE SECURED TO PREVENT FALLING.
08/21/2008 INSP - FULL Violation 3.) TFC 703.1.1 IN THE ELECTRICAL SHOP THERE IS A HOLE IN THE CEILING IN THE SHOP AREA AND A HOLE IN THE CEILING IN THE TECH. LIBRARY THAT NEED TO BE SEALED TO PROVIDE REQUIRED FIREBLOCKING AND DRAFTSTOPPING.
08/21/2008 INSP - FULL Violation 4.) TFC 605.6 IN THE HERMAN MILLER OFFICE SUPPLY STORAGE AREA THERE IS AN ELECTRICAL JUNCTION BOX MISSING A COVER PLATE.
08/21/2008 INSP - FULL Violation 5.) TFC 315.2.1 IN THE HERMAN MILLER OFFICE SUPPLY STORAGE AREA THE SHELF STORAGE NEEDS TO BE LOWERED TO MAINTAIN 18" CLEARANCE BELOW THE SPRINKLER HEADS.
08/21/2008 INSP - FULL Violation 6.) TFC 605.3 IN THE ELECTRICAL SHOP STORAGE SHED THE PORTABLE WORK BENCHES ARE BLOCKING ACCESS TO THE ELECTRICAL PANELS. A 30" WORKING SPACE SHALL BE PROVIDED IN FRONT OF PANELS.
08/21/2008 INSP - FULL Violation 7.) TFC 605.6 UPSTAIRS OF THE EDUCATION BUILDING IN THE PACIFICARE OFFICE THERE IS A COVER PLATE MISSING ON THE ELECTRICAL OUTLET ON THE NORTH WALL.
08/21/2008 INSP - FULL Violation 8.) TFC 703.1.1 IN THE OFFICE ACROSS THE HALL FROM THE PACIFICARE OFFICE A COVER PLATE IS NEEDED TO COVER OPENING IN THE WALL.