Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T08FR02487
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/11/2008 | INSP - FULL | Approved | ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED. | |
08/21/2008 | INSP - FULL | Violation | AREAS INSPECTED: FAST TRACK BUILDING AND EDUCATION BUILDING. FAST TRACK BUILDING: 1.)TFC 703.1.1 THE CEILING TILE IN THE I/S CLOSET HAS HOLES AROUND CABLES THAT NEED TO BE SEALED TO PROVIDE REQUIRED FIREBLOCKING AND DRAFTSTOPPING. |
|
08/21/2008 | INSP - FULL | Violation | EDUCATION BUILDING: 1.) TFC 605.5 THE EXTENSION CORD USED TO POWER THE REFRIGERATOR IN THE PLUMBING SHOP IS NOT ALLOWED TO BE A SUBSTITUTE FOR PERMANENT WIRING. |
|
08/21/2008 | INSP - FULL | Violation | 2.) TFC 3003.5.3 THE COMPRESSED GAS CYLINDERS IN THE PLUMBING SHOP NEED TO BE SECURED TO PREVENT FALLING. | |
08/21/2008 | INSP - FULL | Violation | 3.) TFC 703.1.1 IN THE ELECTRICAL SHOP THERE IS A HOLE IN THE CEILING IN THE SHOP AREA AND A HOLE IN THE CEILING IN THE TECH. LIBRARY THAT NEED TO BE SEALED TO PROVIDE REQUIRED FIREBLOCKING AND DRAFTSTOPPING. | |
08/21/2008 | INSP - FULL | Violation | 4.) TFC 605.6 IN THE HERMAN MILLER OFFICE SUPPLY STORAGE AREA THERE IS AN ELECTRICAL JUNCTION BOX MISSING A COVER PLATE. | |
08/21/2008 | INSP - FULL | Violation | 5.) TFC 315.2.1 IN THE HERMAN MILLER OFFICE SUPPLY STORAGE AREA THE SHELF STORAGE NEEDS TO BE LOWERED TO MAINTAIN 18" CLEARANCE BELOW THE SPRINKLER HEADS. | |
08/21/2008 | INSP - FULL | Violation | 6.) TFC 605.3 IN THE ELECTRICAL SHOP STORAGE SHED THE PORTABLE WORK BENCHES ARE BLOCKING ACCESS TO THE ELECTRICAL PANELS. A 30" WORKING SPACE SHALL BE PROVIDED IN FRONT OF PANELS. | |
08/21/2008 | INSP - FULL | Violation | 7.) TFC 605.6 UPSTAIRS OF THE EDUCATION BUILDING IN THE PACIFICARE OFFICE THERE IS A COVER PLATE MISSING ON THE ELECTRICAL OUTLET ON THE NORTH WALL. | |
08/21/2008 | INSP - FULL | Violation | 8.) TFC 703.1.1 IN THE OFFICE ACROSS THE HALL FROM THE PACIFICARE OFFICE A COVER PLATE IS NEEDED TO COVER OPENING IN THE WALL. |