Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T08FR02482

Parcel: 12901045A


Addresses:

1900 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - UST

Case Number - T08FR02482

Inspection Description - INSP - UST

Inspection Status - Approved

Date Description Inspector Results Comments
09/03/2008 INSP - UST Approved All reports recieved and on file.
08/21/2008 INSP - UST Correction Required Dear Sir or Madam,

The Tucson Fire Department has conducted a fire safety inspection at the above stated business on August 21, 2008. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2006 International Fire Code with modifications. A Re-inspection will be performed on or about September 2, 2008.


2205.2.3 Leak detectors. Leak detection devices required by Section 2206.7.7.1 shall be checked and tested at least annually in accordance with the manufacturer's specifications to ensure proper installation and operation.

· Please provide documentation of test results and ensure all leak detection devices are installed as per the manufacturer.


Section 3404.2.12.3 Existing tanks and piping. Existing underground storage tanks and piping shall be tested for leakage at the owner's or operator's expense at least every 24 months in accordance with this section.

EXCEPTION: Underground storage tank systems with an approved method of detecting leaks from any component of the system.

Tanks shall be emptied of flammable or combustible liquids if required tests are not completed within the specified time.
When testing is required, owners or operators shall provide the fire code official with data setting forth the method of testing that is to be used and shall submit the name of a qualified individual who will conduct the test.

A testing permit shall be obtained. The method of testing to be used shall consider the effects of temperature, pressure and other variables and shall establish conclusively whether the tank or piping is leaking. Pneumatic testing is prohibited.

Devices used for final testing shall be capable of detecting leaks as small as 0.05 gallon per hour. Leaking piping and equipment shall not be used until repaired or replaced. The fire code official is authorized to require that the test be conducted in the code official's presence.

· Please provide a copy of the line leak test results and the ATG calibration. We thank you for keeping such up to date and complete files on site.


3404.2.7.3.3 Vent pipe outlets. Vent pipe outlets for tanks storing Class I, II or IIIA liquids shall be located such that the vapors are released at a safe point outside of buildings and not less than 12 feet (3658 mm) above the adjacent ground level. Vapors shall be discharged upward or horizontally away from adjacent walls to assist in vapor dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or other obstructions

As the tree grows please ensure the vents remain clear. 18 inches is sufficient.