Case: T08FR02439

Parcel: 127040170


Addresses:

4950 E SPEEDWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
09/03/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
08/18/2008 INSP - FULL Violation 1.) TFC 605.4 THE MULTI-PLUG ADAPTER LOCATED BEHIND THE WATER COOLER NEEDS TO BE REPLACED WITH A UL LISTED POWER STRIP WITH OVER CURRENT PROTECTION.
08/18/2008 INSP - FULL Violation 2.) TFC 605.4 THE MULTI-PLUG CUBE ADAPTER AT THE CEILING ABOVE THE WEST BAY IS NOT PERMITTED BY THE FIRE CODE.
08/18/2008 INSP - FULL Violation 3.) TFC 605.5 THE EXTENSION CORD USED TO POWER THE LIGHT IN THE STORAGE ROOM NEXT TO THE OFFICE IS NOT ALLOWED TO BE USED AS A SUBSTITUTE FOR PERMANENT WIRING.
08/18/2008 INSP - FULL Violation 4.) TFC 315.2 STORAGE OF COMBUSTIBLE MATERIALS IN BUILDINGS SHALL BE ORDERLY. THE STORAGE ROOM NEXT TO THE OFFICE NEEDS TO HAVE COMBUSTIBLE MATERIALS STORED IN ORDERLY MANNER TO REDUCE FIRE HAZARDS.
08/18/2008 INSP - FULL Violation 5.) TFC 1028.2 THE EXIT ACCESS WAY FROM STORAGE ROOM AND OFFICE NEED TO BE MAINTAINED FREE FROM OBSTRUCTIONS.
08/18/2008 INSP - FULL Violation 6.) TFC 605.1 TWO OUTLETS AND CONDUIT ON THE EAST WALL OF EAST BAY NEED TO BE RE-SECURED TO THE WALL.
08/18/2008 INSP - FULL Violation 7.) TFC 605.6 THE ELECTRICAL JUNCTION BOX NEAR THE CEILING ON THE SOUTH WALL ABOVE WORKBENCH NEEDS A COVER PLATE AND WIRING MUST TERMINATE WITHIN AN APPROVED BOX.
08/18/2008 INSP - FULL Violation 8.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHER FOR THE SHOP NEEDS HAVE A CURRENT INSPECTION TAG.