Case: T08FR02419

Parcel: 11521017G

Inspection Status: Correction Required

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T08FR02419

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Correction Required

Date Description Inspector Results Comments
08/15/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 904.11.6.3 Cleaning. Hoods, grease-removal devices,
fans, ducts and other appurtenances shall be cleaned at
intervals necessary to prevent the accumulation of
grease. Cleanings shall be recorded, and records shall
state the extent, time and date of cleaning. Such records
shall be maintained on the premises.

_____1.Clean and remove all grease accumulation from all hood systems or provide documentation of such cleaning done within the last 3 months.
08/15/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 906.7 Hangers and brackets. Hand-held portable fire
extinguishers, not housed in cabinets, shall be installed on the
hangers or brackets supplied. Hangers or brackets shall be
securely anchored to the mounting surface in accordance with
the manufacturer’s installation instructions.

_____1.Mount the portable fire extinguisher located in the kitchen.
08/15/2008 VIOL - FIRE PROTECTION SYSTEMS Correction Required TFC 901.6 Inspection, testing and maintenance. Fire detection,
alarm and extinguishing systems shall be maintained in an
operative condition at all times, and shall be replaced or
repaired where defective. Nonrequired fire protection systems
and equipment shall be inspected, tested and maintained or
removed.

_____1.Service and tag the portable fire extinguisher located upstairs.