Case: T08FR02417

Parcel: 127110820


Addresses:

5920 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T08FR02417

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/05/2008 INSP - FULL Approved ALL NOTED TFC VIOLATIONS HAVE BEEN CORRECTED.
08/15/2008 INSP - FULL Violation 1.) TFC 906.2 THE PORTABLE FIRE EXTINGUISHERS IN THE FOLLOWING LOCATIONS NEED A CURRENT INSPECTION TAG:
A.) OUTSIDE OF CONFERENCE ROOM.
B.) SERVICE OFFICE.
C.) PARTS PREP AREA.
08/15/2008 INSP - FULL Violation 2.) TFC 605.5 EXTENSION CORDS BEING USED FOR PERMANENT WIRING IN THE FOLLOWING AREAS ARE NOT PERMITTED BY THE FIRE CODE:
A.) THE REFRIGERATOR IN THE TECH BREAK ROOM.
B.) THE PAINT PREP STALL.
C.) THE REFRIGERATOR IN THE 2nd PREP STALL.
08/15/2008 INSP - FULL Violation 3.) TFCM 605.1 WHERE THE POWER CORD FOR THE PARTS CLEANER CONNECTS ( IN THE SUZUKI SERVICE BAY) THERE IS NO INSUTLATION FOR THE WIRES.
08/15/2008 INSP - FULL Violation 4.) TFC 901.6.2 THE SPRINKLER SYSTEM FOR THE SPRAY BOOTH AREA NEEDS TO HAVE AN ANNUAL INSPECTION.
08/15/2008 INSP - FULL Violation 5.) TFC 1008.1.8 THE PAD LOCK ON THE OUTSIDE OF THE MARKED EXIT DOOR FOR THE SUZUKI SERVICE BAY MUST BE REMOVED.
08/15/2008 INSP - FULL Violation 6.) TFC 3403.5.3 INDIVIDUAL CONTAINERS OF FLAMMABLE LIQUIDS SHALL BE IDENTIFIED, MARKED, LABELED AND PLACARDED IN ACCORDANCE WITH FEDERAL REGULATIONS.
NOTE: ALL INDIVIDUAL CONTAINERS OF FLAMMABLE LIQUIDS MUST HAVE DISPENSER CAPS IN PLACE WHEN NOT IN USE.