Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T08FR02410
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/14/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____1.Remove the extension cord used to power the Vitaminwater frige. NOTE:Replace the extension cord with a fused multiplug adapter. |
|
| 08/14/2008 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes. _____1.All open spaces in the electrical service panel located in the back room shall be covered with an electrical blank. |